This is a mixed journeyman electrician practice test with questions from every part of the exam: theory, wiring methods, services, protection, grounding, motors, special occupancies, and code navigation.
Every question here is based on the 2023 NEC. Some states are on a different edition, so check which one your exam uses.
-
Question 1 of 15
A panelboard has a circuit directory, but it is missing for several circuits and uses vague descriptions that do not indicate what loads are served. This is MOST likely:
Show answerHide answer
Answer: A. Not compliant because circuit identification must be clear, evident, and specific as to purpose
NEC 408.4(A) requires circuit identification to be clear, evident, and specific as to purpose. Missing or vague entries typically do not meet this requirement.
-
Question 2 of 15
Which of the following locations in a dwelling unit generally requires GFCI protection?
Show answerHide answer
Answer: A. Laundry areas
Receptacles in laundry areas of dwelling units require GFCI protection under NEC 210.8(A).
-
Question 3 of 15
For an AC service with one set of service-entrance conductors (no parallel sets), which factor determines the size of the grounding electrode conductor per Table 250.66?
Show answerHide answer
Answer: A. The size of the largest ungrounded service-entrance conductor
Table 250.66 sizes the GEC from the largest ungrounded service-entrance conductor. With parallel sets, you use the equivalent area of the parallel conductors instead. Electrode-specific allowances in 250.66(A) through (C) can reduce the required size.
-
Question 4 of 15
In a 120/240-volt, single-phase, 3-wire system, what current does the neutral conductor carry under normal operation?
Show answerHide answer
Answer: A. The unbalanced current between the two ungrounded conductors, which is zero when the load is balanced
In a 120/240-volt, 3-wire system, the neutral carries the difference between the currents on the two ungrounded conductors. With equal loads on both legs, that difference is zero. The neutral is a grounded conductor, but not every grounded conductor is a neutral; a corner-grounded delta phase conductor is one example.
-
Question 5 of 15
Which NEC subsection addresses entrance to and egress from the required working space for electrical equipment?
Show answerHide answer
Answer: D. 110.26(C)
NEC 110.26(C) covers entrance to and egress from the required working space. 110.26(A)(1) through (A)(3) cover depth, width, and height, and 110.26(A)(4) covers limited access.
-
Question 6 of 15
In an RV park load calculation (551.73), what load is used for each dedicated tent site with only 20-ampere supply facilities?
Show answerHide answer
Answer: A. 600 VA
NEC 551.73(A) uses 600 VA per site for dedicated tent sites with 20-ampere supply facilities, compared to 2,400 VA for RV sites with only 20-ampere supply.
-
Question 7 of 15
A conduit run has two 45° bends and one 90° bend between pull boxes. What is the total degrees of bend?
Show answerHide answer
Answer: A. 180°
Two 45° bends total 90°, plus one 90° bend = 180° total.
-
Question 8 of 15
Which metric prefix means one thousandth (0.001)?
Show answerHide answer
Answer: A. Milli (m)
Milli (m) means 10^-3 (one thousandth).
-
Question 9 of 15
During general-industry machinery servicing under OSHA 1910.147, the primary purpose of lockout/tagout is to prevent:
Show answerHide answer
Answer: A. Unexpected energization or startup of equipment during servicing
Lockout/tagout procedures are intended to prevent unexpected energization, startup, or release of stored energy that could injure workers during servicing or maintenance.
-
Question 10 of 15
A 45 kVA 240V single-phase transformer has a secondary current of approximately:
Show answerHide answer
Answer: A. 188 A
45,000 ÷ 240 ≈ 188A.
-
Question 11 of 15
A meter disconnect installed under 230.82(3) serves as the emergency disconnect for a one-family dwelling. How must it be marked?
Show answerHide answer
Answer: D. EMERGENCY DISCONNECT, METER DISCONNECT, NOT SERVICE EQUIPMENT
NEC 230.85 requires a meter disconnect used as the emergency disconnect to be marked 'EMERGENCY DISCONNECT, METER DISCONNECT, NOT SERVICE EQUIPMENT,' since the service disconnect is located elsewhere.
-
Question 12 of 15
Which NEC article contains the primary requirements for electric vehicle power transfer systems (EV charging equipment)?
Show answerHide answer
Answer: A. Article 625
NEC Article 625 contains requirements for electric vehicle power transfer systems.
-
Question 13 of 15
For sizing branch-circuit conductors, fixed electric space-heating equipment (and any associated motors) is treated as:
Show answerHide answer
Answer: A. A continuous load, with conductors sized at 125% of the load
NEC 424.4(B) requires fixed electric space-heating equipment and any associated motors to be treated as continuous loads for branch-circuit sizing. Under 210.19(A)(1), branch-circuit conductors for continuous loads are sized at 125% of the load.
-
Question 14 of 15
Which cable type is commonly used for underground service laterals?
Show answerHide answer
Answer: A. Type USE (Underground Service-Entrance)
Type USE is Underground Service-Entrance Cable, commonly used for underground service laterals where permitted. USE-2 is rated 90°C wet and dry, but that temperature rating doesn't permit interior wiring; a cable also marked as an interior type, such as RHW-2, can be used inside under that marking.
-
Question 15 of 15
The PRIMARY purpose of an equipment grounding conductor (EGC) is to:
Show answerHide answer
Answer: A. Provide an effective fault current path to facilitate operation of the overcurrent device
EGCs provide a low-impedance path for ground-fault current back to the source so the breaker/fuse opens.
Look at which topics you missed. That tells you where to study next.
Want to focus on one area? Try the grounding, load calc, GFCI and AFCI, ampacity, and Ohm's law practice tests below.